Conduit Fill Chart - Knowing what Conduit Size You Need Based on the Number of Cat5 Cables in Your Cable Run

EMT
| Cat5e | CAT5e Under 24" | Cat6 | Cat6 Under 24" | |
|---|---|---|---|---|
| 1/2 Inch | 4 | 6 | 2 | 3 |
| 3/4 Inch | 7 | 11 | 4 | 6 |
| 1 Inch | 11 | 17 | 6 | 10 |
FMC
| Cat5e | CAT5e Under 24" | Cat6 | Cat6 Under 24" | |
|---|---|---|---|---|
| 3/8 Inch | 1 | 2 | 1 | 1 |
| 1/2 Inch | 4 | 6 | 2 | 3 |
| 3/4 Inch | 7 | 10 | 4 | 6 |
Liquidtight Flexible Nonmetallic Conduit
| Cat5e | CAT5e Under 24" | Cat6 | Cat6 Under 24" | |
|---|---|---|---|---|
| 1/2 Inch | 4 | 6 | 2 | 3 |
| 3/4 Inch | 7 | 11 | 4 | 6 |
PVC, Schedule 40
| Cat5e | CAT5e Under 24" | Cat6 | Cat6 Under 24" | |
|---|---|---|---|---|
| 1/2 Inch | 4 | 6 | 2 | 3 |
| 3/4 Inch | 7 | 10 | 4 | 6 |
| 1 Inch | 11 | 17 | 6 | 9 |
Rigid Metal Conduit
| Cat5e | CAT5e Under 24" | Cat6 | Cat6 Under 24" | |
|---|---|---|---|---|
| 1/2 Inch | 4 | 6 | 2 | 3 |
| 3/4 Inch | 7 | 11 | 4 | 6 |
| 1 Inch | 12 | 18 | 7 | 10 |